Notifier NMM-100 Standard-Sized Module
| Brand | Notifier |
|---|---|
| SKU | NMM-100 |
| Type | Monitor Modules |
| Variants | 1 |
Notifier NMM-100 is a standard-sized addressable monitor module for Notifier FireWarden Series intelligent fire alarm control panels. It supervises a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices and reports its status (open, normal or short) to the panel under its own address.
The module is powered directly by the two-wire SLC loop, identifies itself to the panel as a monitor module, and has a panel-controlled LED that flashes during normal operation and latches on steady in alarm. It supports the LiteSpeed communication protocol.
Specifications
| Operating voltage | 15 to 32 VDC |
| Maximum current | 5.0 mA (LED on) |
| Average operating current | 375 µA (LED flashing, 47k EOL) |
| IDC wiring resistance | 1500 ohms max. |
| IDC voltage | 11 V max. |
| EOL resistance | 47K ohms (provided) |
| Addressing | Rotary switches; 01–99 on FireWarden-100-2, 01–50 on FireWarden-50 |
| Temperature range | 32 °F to 120 °F (0 °C to 49 °C) |
| Humidity | 10% to 93% non-condensing |
| Dimensions | 4.5 in. H x 4 in. W x 1.25 in. D |
Installation notes
- Mounts to a 4 in. square box, 2.125 in. deep.
- SEMS screws with clamping plates for easier wiring.
- Use for four-wire smoke detectors, pull stations, waterflow switches and other normally open contacts, or for normally open supervisory devices.
Related models
- NMM-100P: miniature monitor module, Class B, fits a single-gang box behind the device
- NZM-100: zone module for two-wire 24 V smoke detectors
- NDM-100: dual monitor module, two Class B circuits
- NMM-100-10: ten-input monitor module
Documents
FAQ
Which panels does the NMM-100 work with?
It is a monitor module for Notifier FireWarden Series intelligent control panels. Addresses run 01 to 99 on the FireWarden-100-2 and 01 to 50 on the FireWarden-50.
Can it supervise a Class A circuit?
Yes. The monitored circuit can be wired as an NFPA Style B (Class B) or Style D (Class A) initiating device circuit. The 47K ohm end-of-line resistor is provided for Style B; no resistor is needed for Style D.
What devices can it monitor?
A zone of four-wire smoke detectors, manual pull stations, waterflow devices or other normally open dry-contact devices. It can also monitor normally open supervisory devices.
Does it need separate power?
No. It is powered directly by the two-wire SLC loop.
Questions about this product
Is Notifier NMM-100 Standard-Sized Module in stock?
Yes — 42 units are available and ready to ship from our US warehouse.
How fast will Notifier NMM-100 Standard-Sized Module ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Notifier NMM-100 Standard-Sized Module ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.