TypeSmoke Detectors
Variants1

Notifier FSP-851 — a low-profile intelligent plug-in photoelectric smoke detector with integral communication, compatible with NOTIFIER ONYX and CLIP series Fire Alarm Control Panels.

Detector sensitivity can be programmed in the control panel software, and sensitivity is continuously monitored and reported to the panel. Point ID capability allows each detector’s address to be set with rotary, decimal address switches, providing exact detector location for selective maintenance when chamber contamination reaches an unacceptable level. The FSP-851 photoelectric detector’s unique optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources.

FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by NOTIFIER that greatly increases the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion; if one of the devices in the group has new information, the panel’s CPU stops the group poll and concentrates on single points, giving response speed greater than five times that of earlier designs.

The FSP-851 is a plug-in head that uses a separate base to simplify installation, service and maintenance — the base is ordered separately. A special tool allows maintenance personnel to plug in and remove detectors without using a ladder. The FSP-951 Series is the current direct replacement for the FSP-851 Series, but the 851 remains widely used for service and replacement in existing systems.

Specifications

Sensing technology Photoelectric
Sensitivity 0.5% to 2.35% per foot obscuration
Voltage range 15 – 32 volts DC peak
Standby current (max. avg.) 300 µA @ 24 VDC (one communication every five seconds with LED enabled)
LED current (max.) 6.5 mA @ 24 VDC ("ON")
SLC connection Two-wire; compatible with FlashScan® and CLIP protocol systems
Addressing Rotary, decimal — 1–99 on CLIP systems, 1–159 on FlashScan systems
Height 2.1" (5.3 cm); base determines diameter
Diameter with B210LP(A) base 6.1" (15.5 cm)
Diameter with B501(A) base 4.1" (10.4 cm)
Diameter with B200S(A) / B200SR(A) base 6.875" (17.46 cm)
Diameter with B224RB(A) / B224BI(A) base 6.2" (15.748 cm)
Shipping weight 5.2 oz. (147 g)
Operating temperature range 32°F to 120°F (0°C to 49°C)
Relative humidity 10% – 93% non-condensing
UL/ULC certified velocity range 0 – 4000 ft./min. (1219.2 m/min.), suitable for installation in ducts
Housing Off-white fire-resistant plastic, 94-5V flammability rating
UL certified S1115
ULC certified S1115 (FSP-851A, FSP-851RA, FSP-851TA)
FM Approved
CSFM 7272-0028:0206
MEA 225-02-E
Maryland State Fire Marshal Permit # 2122

Installation notes

  • Base is a separate order: the FSP-851 must be mounted to a compatible base — B210LP(A), B501(A), B200S(A), B200SR(A), B224RB(A) relay or B224BI(A) isolator. For base details see DN-60054.
  • Backbox depth: mount the base on an electrical backbox at least 1.5" (3.81 cm) deep.
  • Wiring: end-of-line resistors are not required because of the inherent supervision provided by the SLC loop. T-taps or branches are permitted for Style 4 (Class B) wiring.
  • Isolator limits: when using relay or sounder bases, consult ISO-X(A) installation sheet I56-1380 for device limitations between isolator modules and isolator bases. A maximum of 25 devices is allowed between B224BI(A) isolator bases.
  • Addressing ceiling differs by protocol: 1–99 on CLIP systems but 1–159 on FlashScan — confirm the loop protocol before assigning addresses above 99.
  • Standby current is higher than the 951: at 300 µA versus 200 µA, loop current budgets calculated for FSP-951 detectors do not transfer directly when retrofitting 851 heads.
  • Relay base ratings (B224RB(A)): Form-C, 2.0 A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive.

Replacement

The Notifier FSP-851 is superseded by the FSP-951, its direct replacement. The FSP-851 remains in wide use as a service and replacement head on existing systems. When swapping, note that the FSP-851 draws 300 µA standby against 200 µA for the FSP-951, and the FSP-951 uses a 2.0 in. profile.

Related models

  • FSP-851A — same detector with ULC certification.
  • FSP-851T / FSP-851TA — adds a built-in 135°F (57°C) fixed-temperature thermal device; operating range narrows to 32°F to 100°F (0°C to 38°C), with a low temperature signal at 45°F ± 10°F.
  • FSP-851R / FSP-851RA — remote test capable for DNR(A)/DNRW duct housings; rated -4°F to 158°F (-20°C to 70°C) when installed in the housing.
  • FSP-951 — the current-generation replacement, with a 2.0" profile, 200 µA standby current and UL 268 7th Edition design.

Specifications taken from the NOTIFIER data sheet "FSP-851(A) Series Intelligent Plug-In Photoelectric Smoke Detectors with FlashScan," document DN-6935:E (2/11/2015). Manufacturer specifications are subject to change without notice.

Documents

FAQ

Is the FSP-851 still available?
Notifier has replaced the FSP-851 Series with the FSP-951 Series, which is a direct replacement. Check the replacement note on this page for current options.

Which bases fit the FSP-851?
B210LP, B501, B200S, B200SR, B224RB and B224BI series bases; the base sets the installed diameter.

Can it be used in a duct detector?
The FSP-851R is the remote-test model used in DNR/DNRW duct housings; the standard FSP-851 has a certified air velocity range of 0–4000 ft/min.

Questions about this product

Is Notifier FSP-851 Photoelectric Sensor in stock?

Yes — 10 units are available and ready to ship from our US warehouse.

How fast will Notifier FSP-851 Photoelectric Sensor ship?

Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.

Where does Notifier FSP-851 Photoelectric Sensor ship from?

It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.

Cart0
Your cart is empty

Have an account? Log in to check out faster.

Continue shopping