Kidde SA-ETH — optional Ethernet interface card for the VS1 and VS4 intelligent fire alarm control panels.

Without it a VS panel is reached through a serial port or a phone line. The SA-ETH gives it a network connection instead, so configuration and history move over the local network and reporting can go to a network receiver in place of a dialer.

  • 10/100 Base-T with auto negotiation; RJ-45 Cat 5 connection, patch or crossover cable
  • Uploads and downloads panel configuration, history and status via the configuration utility
  • Required for TCP/IP communication with a computer running Vigilant Site Monitor
  • 24 VDC; 34 mA standby and alarm, 41 mA maximum; maximum run 200 feet (60 m) of Cat 5
  • Defaults to IP 192.168.001.003, subnet 255.255.255.0; must be configured in programming
  • Four status LEDs: Link, Speed, Duplex, Collision; 32 to 120 °F

It mounts behind the main board and connects to J1 by ribbon cable, taking no device loop slot. The other VS option cards are not substitutes: SA-DACT is the telephone dialer, SA-232 the RS-232 card, SA-CLA the Class A card. SA-FSB, the BMS bridge, needs SA-232.

Questions about this product

Is Kidde SA-ETH Ethernet Interface Card for VS1 and VS4, Programming and Diagnostics in stock?

Yes — 35 units are available and ready to ship from our US warehouse.

How fast will Kidde SA-ETH Ethernet Interface Card for VS1 and VS4, Programming and Diagnostics ship?

Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.

Where does Kidde SA-ETH Ethernet Interface Card for VS1 and VS4, Programming and Diagnostics ship from?

It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.

Cart0
Your cart is empty

Have an account? Log in to check out faster.

Continue shopping