Kidde FX-PDD Intelligent Addressable Optical Duct Detector
| Brand | Kidde |
|---|---|
| SKU | FX-PDD |
| Type | Duct Detectors |
| Variants | 1 |
Kidde FX-PDD is an intelligent addressable duct smoke detector for FX-Series systems. It samples air in the HVAC duct and initiates an alarm when the obscuration of combustion products exceeds its sensitivity setting, giving early warning and helping shut down the HVAC unit so smoke is not circulated through the building.
Air enters the sensing chamber through a sampling tube that extends into the duct and returns through the exhaust tube. The detector uses rotary addressing, issues a dirty sensor warning, and uses differential sensing so gradual dust build-up does not change alarm sensitivity.
Specifications
| Detection method | Photoelectric (light scattering) |
| Smoke sensitivity | 0.79 to 2.46%/ft obscuration |
| Air velocity | 100 to 4,000 ft/min |
| Air pressure differential | 0.005 to 1.00 in. of water |
| Operating current | 45 µA normal and alarm; 1 mA inrush |
| Communication line voltage | 20 V peak-to-peak maximum |
| Auxiliary relay | One Form C alarm relay, unsupervised and power-limited |
| Operating environment | 32 to 120 °F (0 to 50 °C), 0 to 93% RH |
| Dimensions | 8.70 x 5.45 x 1.90 in. |
| Alarm test response | 5 seconds |
Installation notes
- The sampling tube is ordered separately (SD-T8 through SD-T120); the exhaust tube is included.
- Sampling tubes install from the duct side or from inside the sensor compartment and rotate in 45° steps; inlet holes must face the airstream.
- Test duct air velocity, temperature and humidity before installing.
- Use the SD-PH protective housing in high-humidity environments.
- Remote test/reset stations SD-TRM (magnet) and SD-TRK (key), and the R-LED remote alarm LED, are compatible.
Related models
- SD-TRK key-operated remote test/reset station
- SD-TRM magnet-operated remote test/reset station
- SD-T series sampling tubes
Documents
FAQ
Is the sampling tube included?
No. The sampling tube is ordered separately, in lengths such as SD-T8, SD-T18, SD-T24 or SD-T36; the exhaust tube is included.
What air velocity does it need?
100 to 4,000 ft/min.
Can it be tested remotely?
Yes. Magnet-operated (SD-TRM) and key-operated (SD-TRK) one-gang remote test/reset stations are available, and the R-LED remote alarm LED is compatible.
Does it have a relay output?
Yes, one Form C auxiliary alarm relay for controlling equipment such as HVAC controls.
Questions about this product
Is Kidde FX-PDD Intelligent Addressable Optical Duct Detector in stock?
Yes — 18 units are available and ready to ship from our US warehouse.
How fast will Kidde FX-PDD Intelligent Addressable Optical Duct Detector ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Kidde FX-PDD Intelligent Addressable Optical Duct Detector ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.