Kidde FX-1000 FX-Series 4-Loop Addressable Fire Alarm System
| Brand | Kidde |
|---|---|
| SKU | FX-1000 |
| Type | Control Panels |
| Variants | 1 |
Scalable intelligent detection for small to mid-sized buildings is the job of the Kidde FX-1000. This FX-Series control panel ships with one 250-point loop installed and grows to 1,000 points with loop controller cards. It comes as a complete 120 V system with four NACs and a red surface-mount enclosure.
Key Features
- One 250-point Class A or Class B loop (125 detectors + 125 modules) installed
- Expandable to four loops and 1,000 points with FX-SLC1 or FX-SLC2 loop controller modules
- Four NACs (Class B, or two Class A) individually configurable for continuous, temporal, synchronized or coded output
- 4 x 20 character backlit LCD, two programmable switches and rotary device addressing
- Supports up to eight serial annunciators; optional SA-ETH Ethernet and SA-DACT2 dialer
- Pre-alarm, alarm verification by point and adjustable detector sensitivity
Specifications
- Manufacturer: Kidde
- Part Number: FX-1000
- Capacity: 1,000 points (one 250-point loop installed)
- NAC Output: 24 VFWR; 6.0 A total, 2.5 A max. per circuit at 120 VAC 60 Hz
- Primary Power: 120 VAC
- Batteries: 24 VDC SLA; two 18 Ah batteries fit in cabinet; 26 Ah charging capacity
- Enclosure: Surface mount, red
- Operating Environment: 32°F to 120°F (0°C to 49°C), 0–93% RH non-condensing
Compatibility
Supports Kidde intelligent addressable detectors, modules and bases; see the FX-64 and FX-1000 Series Compatibility List (P/N 3102355-EN). The RZI16-2RS module adds up to 16 conventional circuits and two NACs for retrofits.
Documents
FAQ
How many devices does the FX-1000 support?
It ships with one Class A or Class B intelligent device loop for 250 addresses. Loop controller modules expand the system in 250-point increments up to 1,000 device addresses.
How many NACs does it have?
Four NACs that can be wired for Class A or Class B operation.
Can it be connected to a central station over the network?
Yes. The optional SA-ETH Ethernet port supports central monitoring, programming, diagnostics and system reports, and the SA-DACT2 adds a dialer.
Can existing conventional devices be reused?
Yes. The RZI16-2RS zone module adds up to 16 conventional circuits and two NACs, and most retrofit applications can use existing wiring.
Questions about this product
Is Kidde FX-1000 FX-Series 4-Loop Addressable Fire Alarm System in stock?
Yes — 23 units are available and ready to ship from our US warehouse.
How fast will Kidde FX-1000 FX-Series 4-Loop Addressable Fire Alarm System ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Kidde FX-1000 FX-Series 4-Loop Addressable Fire Alarm System ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.