Det-Tronics 012500-212 U5015A2N12A Explosion Proof Smoke Detector
| Brand | Det-Tronics |
|---|---|
| SKU | 012500-212 |
| Type | Smoke Detectors |
| Variants | 1 |
Det-Tronics U5015A2N12A (part number 012500-212) is a U5015 explosion-proof smoke detector with Division and Zone explosion-proof ratings for industrial and commercial hazardous locations. It is designed to respond to both smoldering and rapidly growing fires and to annunciate its own faults, so there are no undisclosed failures.
In the U5015 model matrix, this version is aluminum, with two 3/4 in. NPT ports, 0–20 mA and relay outputs in non-latching mode, and FM/IECEx/CSA approval. Outputs include a 0–20 mA signal, a local LED and three relays, which suits integration with DCS and PLC systems as well as fire panels. The sensor module is field replaceable if it becomes dirty or damaged.
Specifications
| Model | U5015A2N12A, part number 012500-212 |
| Housing | Aluminum, 2 ports, 3/4 in. NPT |
| Outputs | 0–20 mA plus relays, non-latching |
| Operating voltage | 12 to 30 VDC (24 VDC nominal) |
| Power | 3.5 W maximum (2.75 W at 24 VDC) |
| Relays | Alarm Form C, fault Form A, auxiliary Form C; 5 A at 30 VDC resistive |
| Operating temperature | -4°F to +149°F (-20°C to +65°C) |
| Approvals | FM, IECEx, CSA |
Installation notes
- Use the U5015 model matrix to match material, port count, thread and output type
- The fault relay is normally energized; alarm and auxiliary relays are normally de-energized
- Unused entries take 3/4 in. NPT aluminum stop plugs (101197-001)
- Replacement sensor module: 104286-003
- The detector is not field repairable; return it to the factory for repair
Related models
- U5015A4N12A (012500-214): 4-port version
- U5015A2N13A (012500-202): latching version
- U5015A1N12A (012500-211)
Documents
FAQ
What does the model code U5015A2N12A mean?
Per the U5015 model matrix: A is aluminum, 2 is two ports, N is 3/4 in. NPT threads, 12 is 0–20 mA and relay outputs, non-latching, and A is FM/IECEx/CSA approval.
What supply voltage does it need?
12 to 30 VDC, 24 VDC nominal, with 3.5 W maximum power consumption.
Can the sensor be replaced in the field?
Yes. The sensor module is field replaceable (replacement part 104286-003); the detector itself is not field repairable and goes back to the factory for repair.
What are the relay ratings?
All relays are rated 5 A at 30 VDC resistive: a Form C alarm relay, a Form A fault relay and a Form C auxiliary relay.
Questions about this product
Is Det-Tronics 012500-212 U5015A2N12A Explosion Proof Smoke Detector in stock?
Yes — 15 units are available and ready to ship from our US warehouse.
How fast will Det-Tronics 012500-212 U5015A2N12A Explosion Proof Smoke Detector ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Det-Tronics 012500-212 U5015A2N12A Explosion Proof Smoke Detector ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.